Task Force on Harmonics Modeling and Simulation*
Transmission & Distribution Committee
IEEE Power Engineering Society
Task force members and contributors are: R. Abu-hashim, R. Burch, G. Chang, M. Grady, E. Gunther, M. Halpin, C. Hatziadoniu, Y. Liu, M. Marz, T. Ortmeyer, V. Rajagopalan, S. Ranade, P. Ribeiro (vice chair), T. Sims, W. Xu (chair, editor).Abstract - This paper presents three harmonic simulation test systems. The purpose is to demonstrate guidelines for the preparation and analysis of harmonic problems through case studies and simulation examples. The systems can also be used as benchmark systems for the development of new harmonic simulation methods and for the evaluation of existing harmonic analysis software.
10.1 Introduction
Harmonic studies have become an important aspect of power system analysis and design in recent years. Harmonic simulations are used to quantify the distortion in voltage and current waveforms in a power system and to determine the existence and mitigation of resonant conditions. Many digital computer programs are available for harmonic analysis. New analysis techniques are being developed. With a wide variety of solution methods and modeling assumptions implemented in many different programs, there is a need for benchmark test systems so that the features and results of the programs can be evaluated and compared.
This paper presents the complete data for three harmonic simulation test systems. The purpose is to demonstrate guidelines for the preparation and analysis of harmonic problems through case studies and simulation examples. Several aspects that can impact the accuracy of results such as modeling of components and solution methods are illustrated. The benchmark information provided in the paper is also useful for the development of new harmonic simulation methods and for the evaluation of existing harmonic analysis software. The test systems represent the most common harmonic study scenarios encountered in industry. Sample results are provided in the paper. More information on the test systems and results can be obtained at http://www.ee.ualberta.ca/pwrsys/harmonics.html *.
* Editors' Note: It is not guaranteed that the web page will always be available. Therefore, the test systems are given in the Appendix Section B.
10.2 Test System No.1: A 14-Bus Balanced Transmission System
This test system contains two harmonic sources. One is a twelve-pulse HVDC terminal at bus 3 and the other is a SVC at bus 8 (Figure 10.1 and Figure 10.2). Because the system has balanced bus loads and the transmission lines are transposed, a balanced harmonic analysis is generally sufficient for determining harmonic distortion levels in this case. Main harmonic analysis issues to be demonstrated by this test system are:
Figure 10.1. Test System 1 - 14 Bus Transmission System
Figure 10.2. Harmonic Sources in Test System 1
Complete data for this system are shown in Tables 10.1 to 10.4. Key modeling and simulation features for this case are:
(Click on the graphic, to view it in a larger size)
Figure 10.3. Effects of using different line models
Table 10.1 Bus Data and Results for System 1

Table 10.2: Branch Data for System 1 (Based on 100MVA)
Table 10.3: Generator Data for System 1

Table 10.4. Harmonic Source Data for System 1
10.3 Test System No.2: A 13-Bus Unbalanced Utility Distribution System
This system is based on the IEEE 13 bus radial distribution test feeder [4]. The system is unbalanced and serves as a benchmark system for unbalanced harmonic propagation studies. The system was used in [1] for illustrative purposes and, with additional modifications, is proposed here as a harmonics test system.
The feeder, shown in Figure 10.4, contains voltage regulators, three and single phase line configurations, shunt capacitors, and spot and distributed loads. Phase-ground and phase-phase connected loads are included. For harmonic studies, load compositions are specified to include harmonic producing loads. Complete data are provided in the Appendix A*. Current spectra for the three load types, namely fluorescent light banks, adjustable speed drives, and composite ("other") residential loads, are given for test purposes. The analysis of harmonic propagation in distribution systems must necessarily utilize a phase-domain representation. The following items must be considered in the analysis of unbalanced distribution systems:
* Editors Note: Click here to link to the data for Test System II.
As demonstrated in [1], relatively moderate variations in the models can have a significant impact on results. The test system is specified in a way that highlights all of these issues. The Alternative Transients Program was used to calculate harmonic propagation in the system [5,6]. Partial results are shown in Table 10.5 and Figure 10.5.

Figure 10.4. Test System 2 - Unbalanced Distribution System
Table 10.5. Voltage THD (Fundamental Frequency Component)
| Node # | Phase A | Phase B | Phase C |
| 32 | 1.96(1.034) | 1.76 (1.038) | 1.69(1.007) |
| 33 | 1.96(1.034) | 1.76(1.038) | 1.69(1.007) |
| 34 | 0.96(1.018) | 0.96(1.030) | 1.04(1.022) |
| 71 | 3.23(1.010) | 2.76(1.045) | 2.86(0.969) |
| 75 | 3.35(1.003) | 2.82(1.048) | 2.95(0.967) |
| 52 | 3.30(1.008) | ||
| 911 | 3.00(0.965) |

Figure 10.5.Harmonic Voltage Distortion Spectrum at Node 71
Modeling and simulation features for this case are:
For the case studied, the voltage distortion levels are low. This is because several loads are connected phase-phase and harmonic phase angles are modeled. As described in reference [1], significantly different results are obtained depending on the choice of load models and harmonic current source models. It is noted that in the examples in [1], all loads were assumed to be connected phase-ground, the motor and capacitor at node 34 are in service and harmonic source spectra were different from the ones used here.
nbsp;
10.4 Test System No.3: A 13-Bus Balanced Industrial Distribution System
This test case consists of 13 buses and is representative of a medium-sized industrial plant. The system is extracted from a common system that is being used in many of the calculations and examples in the IEEE Color Book series [7]. The plant is fed from a utility supply at 69 kV and the local plant distribution system operates at 13.8 kV. The system is shown in Figure 10.6 and described by the data in Tables 10.6-10.9. Due to the balanced nature of this example, only positive sequence data is provided. Capacitance of the short overhead line and all cables are neglected.

Figure 10.6. Test System 3 - A Balanced Industrial System
Additional data used to conduct a harmonic analysis of the example industrial system include the following:
Table 10.6. Per-Unit Line and Cable Impedance Data (base values: 13.8 kV, 10,000 kVA)
From |
To |
R |
X |
100: UTIL-69 |
01:69-1 |
0.00139 |
0.00296 |
03:MILL-1 |
50:GEN-1 |
0.00122 |
0.00243 |
03:MILL-1 |
05:FDR F |
0.00075 |
0.00063 |
03:MILL-1 |
26:FDR G |
0.00157 |
0.00131 |
03:MILL-1 |
06:FDR H |
0.00109 |
0.00091 |
From |
To |
Voltage |
Tap |
kVA |
%R |
%X |
01:69-1 |
03:MILL-1 |
69:13.8 |
69 |
15000 |
0.4698 |
7.9862 |
50:GEN1 |
51:AUX |
13.8:0.48 |
13.45 |
1500 |
0.9593 |
5.6694 |
05:FDR F |
49:RECT |
13.8:0.48 |
13.45 |
1250 |
0.7398 |
4.4388 |
05:FDR F |
39:T3 SEC |
13.8:4.16 |
13.11 |
1725 |
0.7442 |
5.9537 |
26:FDR G |
29:T11 SEC |
13.8:0.48 |
13.45 |
1500 |
0.8743 |
5.6831 |
06:FDR H |
11:T4 SEC |
13.8:0.48 |
13.8 |
1500 |
0.8363 |
5.4360 |
06:FDR H |
19:T7 SEC |
13.8:2.4 |
13.11 |
3750 |
0.4568 |
5.4810 |
Table 10.8. Generation, Load, and Bus Voltage Data (from power flow study results)
Bus |
Vmag (p.u.) |
d (deg) |
Pgen kW |
Qgen kvar |
Pload kW |
Qload kvar |
100:UTIL-69 |
1.000 |
0.00 |
7450 |
540 |
- |
- |
01:69-1 |
0.999 |
-0.13 |
- |
- |
- |
- |
03:MILL-1 |
0.994 |
-2.40 |
- |
- |
2240 |
2000 |
50:GEN1 |
0.995 |
-2.39 |
2000 |
1910 |
- |
- |
51:Aux |
0.995 |
-3.53 |
- |
- |
600 |
530 |
05:FDR F |
0.994 |
-2.40 |
- |
- |
- |
- |
49:RECT |
0.980 |
-4.72 |
- |
- |
1150 |
290 |
39:T3 SEC |
0.996 |
-4.85 |
1310 |
1130 |
||
26:FDR G |
0.994 |
-2.40 |
- |
- |
- |
- |
06:FDR H |
0.994 |
-2.40 |
- |
- |
- |
- |
11:T4 SEC |
0.979 |
-3.08 |
- |
- |
370 |
330 |
19: T7 SEC |
1.001 |
-4.69 |
- |
- |
2800 |
2500 |
29:T11 SEC |
0.981 |
-4.16 |
- |
- |
810 |
800 |
Table 10.9. Harmonic Source Data
Harmonic # |
Percent |
Relative Angle |
1 |
100.00 |
0.00 |
5 |
18.24 |
-55.68 |
7 |
11.90 |
-84.11 |
11 |
5.73 |
-143.56 |
13 |
4.01 |
-175.58 |
17 |
1.93 |
111.39 |
19 |
1.39 |
68.30 |
23 |
0.94 |
-24.61 |
25 |
0.86 |
-67.64 |
29 |
0.71 |
-145.46 |
31 |
0.62 |
176.83 |
35 |
0.44 |
97.40 |
37 |
0.38 |
54.36 |
Specific issues related to modeling for harmonic analysis must also be considered if the results presented here are to be obtained using different analysis programs. Modeling considerations applicable to this example include:
The results of a harmonic analysis of the system of Figure 10.6 are given in Table 10.10. Fundamental, fifth, and seventh voltage harmonic amplitudes and THDV are given for each of the system buses. These results, along with those obtained from a fundamental frequency power flow study (shown in Table 10.8), give an accurate description of the voltage profiles in the plant.
Complete data for three harmonic test systems has been presented in this chapter. The systems can be used as benchmark systems for the development of new harmonic analysis methods and for the evaluation of existing harmonic software. Researchers, developers and users of harmonic analysis programs are encouraged to use these systems to test their programs and report their comments to the IEEE PES Harmonics Modeling and Simulation Task Force.
Table 10.10: Plant Harmonic Voltage Distortion Summary.
Bus |
V1 (VLN) |
V5 (VLN) |
V7 (VLN) |
THDV (%) |
|
100:UTIL-69 |
39645.70 |
40.37 |
104.23 |
0.28 |
|
01:69-1 |
39538.00 |
52.36 |
135.14 |
0.37 |
|
03:MILL-1 |
7712.77 |
53.51 |
138.13 |
1.93 |
|
50:GEN1 |
7726.55 |
51.72 |
133.51 |
1.87 |
|
51:Aux |
262.74 |
1.72 |
4.40 |
1.81 |
|
05:FDR F |
7709.24 |
54.07 |
138.35 |
1.94 |
|
49:RECT |
269.89 |
12.79 |
12.83 |
8.02 |
|
39:T3 SEC |
2240.05 |
14.83 |
37.21 |
1.80 |
|
26:FDR G |
7709.07 |
53.48 |
138.04 |
1.93 |
|
06:FDR H |
7703.35 |
53.43 |
137.91 |
1.93 |
|
11:T4 SEC |
260.40 |
1.78 |
4.59 |
1.90 |
|
19: T7 SEC |
1302.74 |
8.58 |
21.78 |
1.81 |
|
29:T11 SEC |
256.29 |
1.71 |
4.36 |
1.84 |
|
The Task Force would like to acknowledge the support of the IEEE PES Harmonics Working Group chaired by Mr. T. Gentile. Case 1 was prepared by W. Xu, Case 2 by S.J. Ranade, and Case 3 by M. Halpin. Results were verified by R. Burch, M. Halpin, C.J. Hatziadoniu, and T.H. Ortmeyer.